Raised Access Floor
The FIREFLY® FB180 Raised Access Floor fire protection system provides a fully tested solution for fire-rated raised access floors. Designed to maintain compartmentation and prevent the spread of fire, the system has been rigorously tested with Kingspan RMG 600 and 18mm OSB Board flooring materials. Offering up to 240 minutes of integrity and 120 minutes of insulation, it is ideal for high-risk voids where fire protection is critical.
USE AREAS
- Raised access floor systems for commercial/industrial buildings
- Data centres and server rooms
- Offices and high-rise buildings requiring compartmentation
- Environments with high fire safety requirements
- Infrastructure projects, e.g., airports, rail stations & tunnels
APPLICATION
The FIREFLY® Raised Access Floor system is engineered for installation in both fire-rated and non fire-rated raised access floor applications. It maintains the compartment line while accommodating necessary penetrations such as Cable trays and data cables, maintaining compartmentation. Suitable for a wide range of environments, including:
- Commercial buildings: Offices, shopping centres, and public facilities requiring protected service voids beneath raised floors.
- Data centres & server rooms: Ensuring fire compartmentation where sensitive electronic equipment is housed.
- Industrial & manufacturing facilities: Providing fire protection in areas with extensive cabling and mechanical penetrations.
- High-rise buildings & residential complexes: Critical for ensuring fire containment in multi-level structures.
- Transport hubs & infrastructure projects: Rail stations, airports, and tunnels where fire-rated access floors are essential.
CONSTRUCTION
Rigorously tested for use with Kingspan RMG 600 and 18mm OSB Board flooring. The FIREFLY® FB180 Ablative 60mm Batt is tested to achieve up to E240 EI120 and up to EI60 on penetrations. This makes it an ideal solution for achieving fire- rated raised access floors up to 600mm in height without additional structural modifications. For full technical details, installation guidelines, and fire test certification, please refer to the official FIREFLY® technical documentation or contact our support team.
KEY BENEFITS
- Achieves up to 180 minutes integrity and 120 minutes insulation with Kingspan RMG 600
- Achieves up to 240 minutes integrity and 120 minutes insulation with OSB Board
- Fully tested with FIREFLY® FB180 Ablative Batt Wall System
- EI60 compliance with penetrations
- Ideal for single batt installation to achieve EI60 Fire resistance
- Provides effective fire compartmentation without compromising access floor functionality
- Compatible with multiple penetration types tested within the FIREFLY® Batt system
TITLE
FIREFLY® Raised Access Floor
TESTING
BS EN 1366-4 & BS EN 1366-3
FIRE RATING
To 240 minutes
CERTIFICATION
Classification Number WF 550732. Third party certified by IFCC/KIWA, certificate number 25611
APPLICATION
Raised access floor systems are suitable for vertical applications in commercial and industrial buildings, including data centres and server rooms, offices and high-rise buildings requiring compartmentation, environments with high fire safety standards, and infrastructure projects
such as airports, railway stations, and tunnels. For specific installation details, please refer to the installation drawings
PROPERTIES
Layered mineral fibre, ablative coating on both sides, white appearance. Density 180kg/m3
ACOUSTICS
27dB sound reduction
DIMENSIONS
1200 x 600 x 60mm
PACKAGING
Supplied bagged to provide protection in transit and on site. Do not allow the batt to be exposed to rain.
PRODUCT CODES
FB180 60mm
LIMITATIONS
Not to be installed in areas of RH >85% Storage: cool, dry place – protect from frost
FB180 was ideal due to the fact that the work had to be carried out from above as there was no possibility of getting access to the science laboratory below.
Please contact technical@tbafirefly.com to request specific CAD files